HUBBELL POWER SYSTEMS
Image of 550-012-B-113-00 SDC™ Bushing Model 0113-00 145kV 550kV BIL1200A
*Representative image
Image of 550-012-B-113-00 SDC™ Bushing Model 0113-00 145kV 550kV BIL1200A
play
Factory Tour: St. Jerome - Hubbell Power Systems

SDC™ Bushing Model 0113-00 145kV 550kV BIL1200A

Brand: Electro Composites

Catalog ID: 550-012-B-113-00

SDC™ 145kV 1200A OCB Bushing, Bottom connected for Air to Oil application, 23.8in ground shield, 175in creep, rated per IEC 60137

Electro Composites SDC™ composite bushings are designed to provide the toughest, cleanest and safest bushing solution for all HV applications. We make standard OEM and aftermarket form-fit-function replacement bushings for substation transformers, GSU transformers, oil circuit breakers, switchgear, wall/floor (air-air and oil-oil), HVDC and other applications. Available from 1kV up to 170kV with current ratings up to 21,500A. SDC™ (Solid Dielectric Capacitor) bushings have a one-piece cycloaliphatic epoxycore and integral sheds. All SDC bushings are solid dielectric insulation – oil–free construction, capacitance graded condenser core with internal CT pocket/ground shield and a flange test tap, available in bottom connected or draw-lead configurations. Made in accordance with the most current bushing standards: IEEE C57.19.01, CSA C88.1, IEC 60137.

  • SDC™ - Solid Dielectric Capacitance Graded Composite Construction
  • EC-APG-02 Cycloaliphatic Epoxy Compound for Optimal Performance
  • No oil, paper or porcelain
  • Can be mounted vertically or horizontally
  • Meets IEC 60137 Electrical and Mechanical Requirements

For Bushing Test Terminals, please see here

General

Application

OCB

Bottom Terminal Type

2 1/4-12

Catalog Number

550-012-B-113-00

Color

Gray

Immersion Type - Above Flange

Air

Immersion Type - Below Flange

Oil

Material - Flange

Aluminum

Material - Insulation

APG-02 - Cycloaliphatic Epoxy

Mounting Position

Vertical to Horizontal

Number of Flange Mounting Holes

6

Product Type

Traversée condensatrice SDC

Series

SDC™

Test Tap

Yes

Top Terminal Type

1 1/2-12

Type

SDC - Solid Dielectric Capacitor

Dimensions

Above Flange Length

69.6 in

Below Flange Length

56.1 in

Depth

17 in

Diameter - Above Flange Maximum

11.38 in

Diameter - Below Flange Maximum D <gt/> 1"

9 in

Diameter - Below Flange Maximum P

9 in

Diameter - Conductor Outside Under Insulation

1.5 in

Diameter - Live Part Bottom

5 in

Diameter - Live Part Top

5 in

Diameter - Rod / Tube

1.5 in

Dimensions

125.7 in x 17 in x 17 in

Effective Length - Bottom Terminal

3.25 in

Effective Length - Top Terminal

4 in

Flange Mounting Hole Bolt Circle

15.5 in

Flange Mounting Hole Diameter

0.91 in

Flange Outside Diameter

17 in

Height

17 in

Length

125.7 in

Length - Ground Shield

23.8 in

Length - Insulated Section

114.9 in

Length - Insulation Above Flange

56.7 in

Length - Insulation Below Flange

28.1 in

Length - Live Part Bottom

4.2 in

Length - Live Part Top

6.62 in

Length - Minimum Oil Immersion Level

23.8 in

Sealing Surface Inside Diameter

9 in

Sealing Surface Outside Diameter

13.63 in

Thickness

3.75 in

Top Terminal Min. Thread Length

4 in

Weight

478 lb

Width

17 in

Electrical Ratings

BIL

550 kV

Current Rating

1200 A

kV Class

145 kV

Minimum Creepage

175 in

Minimum Strike

60 in

Withstand Voltage - 60 Hz Dry

230 kV

Certifications And Compliance

Industry Standard(s)

IEC 60137

Operational

Immersion Type - Above Flange

Air

Immersion Type - Below Flange

Oil

Configuration

Bottom Terminal Type

2 1/4-12

Mounting Position

Vertical to Horizontal

Number of Flange Mounting Holes

6