HUBBELL POWER SYSTEMS
Image of 075-025-T-390-00 SDC™ Bushing Model 0390-00 8.7kV 75kV BIL2500A
*Representative image
Image of 075-025-T-390-00 SDC™ Bushing Model 0390-00 8.7kV 75kV BIL2500A
play
Factory Tour: St. Jerome - Hubbell Power Systems

SDC™ Bushing Model 0390-00 8.7kV 75kV BIL2500A

Brand: Electro Composites

Catalog ID: 075-025-T-390-00

SDC™ 8.7kV 2500A Transformer Bushing, Bottom connected for Air to Oil application, 12in ground shield, 21.2in creep, rated per IEEE C57.19.01

Electro Composites SDC™ composite bushings are designed to provide the toughest, cleanest and safest bushing solution for all HV applications. We make standard OEM and aftermarket form-fit-function replacement bushings for substation transformers, GSU transformers, oil circuit breakers, switchgear, wall/floor (air-air and oil-oil), HVDC and other applications. Available from 1kV up to 170kV with current ratings up to 21,500A. SDC™ (Solid Dielectric Capacitor) bushings have a one-piece cycloaliphatic epoxycore and integral sheds. All SDC bushings are solid dielectric insulation – oil–free construction, capacitance graded condenser core with internal CT pocket/ground shield and a flange test tap, available in bottom connected or draw-lead configurations. Made in accordance with the most current bushing standards: IEEE C57.19.01, CSA C88.1, IEC 60137.

  • SDC™ - Solid Dielectric Capacitance Graded Composite Construction
  • EC-APG-02 Cycloaliphatic Epoxy Compound for Optimal Performance
  • No oil, paper or porcelain
  • Can be mounted vertically or horizontally
  • Meets IEEE C57.19.01 Electrical and Mechanical Requirements

For Bushing Test Terminals, please see here

General

Application

Transformer

Bottom Terminal Type

1.500 Dia Smooth

Catalog Number

075-025-T-390-00

Color

Gray

Immersion Type - Above Flange

Air

Immersion Type - Below Flange

Oil

Material - Flange

Aluminum

Material - Insulation

APG-02 - Cycloaliphatic Epoxy

Mounting Position

Vertical to Horizontal

Number of Flange Mounting Holes

4

Product Type

Traversée condensatrice SDC

Series

SDC™

Test Tap

Yes

Top Terminal Type

2-12

Type

SDC - Solid Dielectric Capacitor

Dimensions

Above Flange Length

12.75 in

Below Flange Length

20.38 in

Depth

7.5 in

Diameter - Above Flange Maximum

8.64 in

Diameter - Below Flange Maximum D <gt/> 1"

3.48 in

Diameter - Below Flange Maximum P

4.34 in

Diameter - Conductor Outside Under Insulation

2 in

Diameter - Live Part Bottom

2 in

Diameter - Live Part Top

3.5 in

Diameter - Rod / Tube

2 in

Dimensions

33.13 in x 7.5 in x 7.5 in

Effective Length - Bottom Terminal

2.5 in

Effective Length - Top Terminal

2 in

Flange Mounting Hole Bolt Circle

6.25 in

Flange Mounting Hole Diameter

0.63 in

Flange Outside Diameter

7.5 in

Height

7.5 in

Length

33.13 in

Length - Ground Shield

12 in

Length - Insulated Section

26.93 in

Length - Insulation Above Flange

6.6 in

Length - Insulation Below Flange

5.09 in

Length - Live Part Bottom

3.29 in

Length - Live Part Top

2.9 in

Length - Minimum Oil Immersion Level

12 in

Sealing Surface Inside Diameter

4.37 in

Sealing Surface Outside Diameter

5.25 in

Thickness

0.74 in

Top Terminal Min. Thread Length

2 in

Weight

55 lb

Width

7.5 in

Electrical Ratings

BIL

75 kV

Current Rating

2500 A

kV Class

8.7 kV

Minimum Creepage

21.2 in

Minimum Strike

8.98 in

Withstand Voltage - 60 Hz Dry

28 kV

Certifications And Compliance

Industry Standard(s)

IEEE C57.19.01

Operational

Immersion Type - Above Flange

Air

Immersion Type - Below Flange

Oil

Configuration

Bottom Terminal Type

1.500 Dia Smooth

Mounting Position

Vertical to Horizontal

Number of Flange Mounting Holes

4