Brand: OHIO BRASS
Catalog ID: SVN168CA131AA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN168CA131AA
Color
Gray Housing
Material
Silicone Polymer Housing
Mounting Position
Upright
Product Type
SVN
Type
Station
Bolt Circle Diameter
10 in
Depth
11.2 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Single Bolt Hole(s)
0.56 in
Height
76.8 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
739 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
850 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
11.2 in
Creep and Leakage Distance
197.2 in (5010 mm)
Duty Cycle
168 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
412 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
322.0 kV
Maximum Switching Surge Protective Level @ 2000A
334.0 kV
Maximum Switching Surge Protective Level @ 500A
313 kV
MCOV
131 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
435 kVrms
Withstand Voltage - Lightning Impulse
838 kV
Withstand Voltage - Switching Impulse
724 kV
Conductor Type
Aluminum/Copper
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position
Upright