Brand: OHIO BRASS
Catalog ID: SVN192CA152AA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN192CA152AA
Color
Gray Housing
Material
Silicone Polymer Housing
Mounting Position
Upright
Product Type
SVN
Type
Station
UPC
096359753575
Bolt Circle Diameter
10 in
Depth
25 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Single Bolt Hole(s)
0.56 in
Height
83.1 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
864 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
991 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
25 in
Creep and Leakage Distance
226.8 in (5760 mm)
Duty Cycle
192 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
479 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
374.0 kV
Maximum Switching Surge Protective Level @ 2000A
387.0 kV
Maximum Switching Surge Protective Level @ 500A
363 kV
MCOV
152 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
498 kVrms
Withstand Voltage - Lightning Impulse
928 kV
Withstand Voltage - Switching Impulse
829 kV
Conductor Type
Aluminum/Copper
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position
Upright