Brand: OHIO BRASS
Catalog ID: SVN228CA180AA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN228CA180AA
Color
Gray Housing
Material
Silicone Polymer Housing
Mounting Position
Upright
Product Type
SVN
Type
Station
UPC
096359891796
Bolt Circle Diameter
10 in
Depth
25 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Single Bolt Hole(s)
0.56 in
Height
90.8 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
1029 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
1177 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
25 in
Creep and Leakage Distance
255.9 in (6500 mm)
Duty Cycle
228 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
566 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
443.0 kV
Maximum Switching Surge Protective Level @ 2000A
458.0 kV
Maximum Switching Surge Protective Level @ 500A
430 kV
MCOV
180 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
559 kVrms
Withstand Voltage - Lightning Impulse
1043 kV
Withstand Voltage - Switching Impulse
930 kV
Conductor Type
Aluminum/Copper
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position
Upright