Brand: OHIO BRASS
Catalog ID: SVN240GA190AA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN240GA190AA
Color
Gray Housing
Material
Silicone Polymer Housing
Mounting Hardware
Single Eyebolt Terminals
Mounting Position
Upright
Product Type
SVN
Type
Station
UPC
096359622765
Bolt Circle Diameter
10 in
Depth
25 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Ring
25 in / 15 in
Diameter - Single Bolt Hole(s)
0.56 in
Height
98.5 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
1089 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
1245 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
25 in
Creep and Leakage Distance
285 in (7240 mm)
Duty Cycle
240 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
598 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
467.0 kV
Maximum Switching Surge Protective Level @ 2000A
484.0 kV
Maximum Switching Surge Protective Level @ 500A
453 kV
MCOV
190 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
620 kVrms
Withstand Voltage - Lightning Impulse
1158 kV
Withstand Voltage - Switching Impulse
1032 kV
Conductor Type
Aluminum/Copper
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position