Brand: OHIO BRASS
Catalog ID: SVN258CA209AA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN258CA209AA
Color
Gray Housing
Material
Silicone Polymer Housing
Mounting Position
Upright
Product Type
SVN
Type
Station
UPC
096359891819
Bolt Circle Diameter
10 in
Depth
39 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Single Bolt Hole(s)
0.56 in
Height
105 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
1202 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
1373 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
39 in
Creep and Leakage Distance
314.6 in (7990 mm)
Duty Cycle
258 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
657 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
514.0 kV
Maximum Switching Surge Protective Level @ 2000A
532.0 kV
Maximum Switching Surge Protective Level @ 500A
499 kV
MCOV
209 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
659 kVrms
Withstand Voltage - Lightning Impulse
1259 kV
Withstand Voltage - Switching Impulse
1096 kV
Conductor Type
Aluminum/Copper
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position
Upright