Brand: OHIO BRASS
Catalog ID: SVN036GA029BA
IEEE Polymer station class surge arrester for substation applications
Application
Station
Cantilever Bending Strength - Max.
70000 in lbs
Catalog Number
SVN036GA029BA
Color
Gray Housing
Material
Silicone Polymer Housing
Mounting Position
Upright
Product Type
SVN
Type
Station
UPC
096359841319
Bolt Circle Diameter
10 in
Depth
11.2 in
Diameter - Lug Hole
0.56 in (14 mm)
Diameter - Single Bolt Hole(s)
0.56 in
Height
38.1 in
Minimum Mounting Spacing on Center (Sea Level) - Phase to
133 mm
Minimum Mounting Spacing on Center (Sea Level)- Phase to Phase
165 mm
Thickness - Lug
0.25 in (7 mm) - 0.81 in (21 mm)
Width
11.2 in
Creep and Leakage Distance
83.9 in (2130 mm)
Duty Cycle
36 kV
Frequency Rating
48-62 Hz
Maximum .5 Microsecond Discharge Volts @ Classifying Current
92 kV
Maximum Discharge Voltage
Maximum Switching Surge Protective Level @ 1000A
72.0 kV
Maximum Switching Surge Protective Level @ 2000A
74.5 kV
Maximum Switching Surge Protective Level @ 500A
69.5 kV
MCOV
29 kV
Pressure Relief Capability-Symmetrical rms (kA)
65
Withstand Voltage - 60 Hz Wet
186 kVrms
Withstand Voltage - Lightning Impulse
374 kV
Withstand Voltage - Switching Impulse
309 kV
Conductor Type
Aluminum/Copper
Industry Standard(s)
IEEE
Cantilever Bending Strength - Max.
70000 in lbs
Maximum Operating Altitude
12000 ft
Mounting Position
Upright